Item #468-288, Model 468 AC Voltage Transformers - Weschler
Weschler Model 468 Voltage Transformers: Single Phase; Accuracy: 0.6%@7.5 VA; Thermal Rating:75VA: These transformers are encased in a thermoplastic case with the core and windings encapsulated in resin. They are designed for line-to-line operation but may also be used in line-to-neutral or line-to-ground configuration at 58% of rated voltage.
It is recommended that a 0.80 Amp fuse be used in the secondary to protect the transformer
- 600V Insulation Level, 10kV BIL
- Accuracy Class 0.6W
- 75VA at 30°C, 50VA at 55°C
- 60Hz
- CSA & UR Approved
Terminals are brass studs No. 10-32 with one lockwasher, flatwasher and regular nut.
Specifications
Voltage Rating (line to line)
288:120
Turns Ratio
2.4:1