Weschler Model 468 Voltage Transformers: Single Phase; Accuracy: 0.6%@7.5 VA; Thermal Rating:75VA: These transformers are encased in a thermoplastic case with the core and windings encapsulated in resin. They are designed for line-to-line operation but may also be used in line-to-neutral or line-to-ground configuration at 58% of rated voltage.

It is recommended that a 0.80 Amp fuse be used in the secondary to protect the transformer

  • 600V Insulation Level, 10kV BIL
  • Accuracy Class 0.6W
  • 75VA at 30°C, 50VA at 55°C
  • 60Hz
  • CSA & UR Approved

Terminals are brass studs No. 10-32 with one lockwasher, flatwasher and regular nut.

Weschler 468 specs

Weschler-468-Specs                              Weschler-468-Datasheet

Request a Quote

Specifications

Voltage Rating (line to line)
240:120
Turns Ratio
2:1